Construction

Conductor            : plain copper wire, stranded.

Insulation             : XLPE compound, (RE-2X….).

Core identification : black / white cores numbered 1-1, 2-2,…
Pair                     : two conductors twisted to a pair.

Lay-up                 : pairs laid up in layers of optimum pitch.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Inner sheath         : PVC compound, flame retardant.

Armour                : galvanized round steel wire.

Outer sheath         : PVC compound, 90° C.
Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2X(St)YSWAY-fl 
 MP 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 300 V
 
Technical data and tests


Rated voltage                      : 300 V.

Test voltage                        : Urms core-core   : 1500 V;

                                          Urms core-screen : 1500 V.

Temperature range              : operation   : - 30° C ~ + 90° C;

                                          installation :   - 5° C ~ + 50° C.

Min. bending radius             : 10 x D.

Insulation resistance            : min. 5000 MΩ/km.

Capacitance unbalanced       : (1 kHz) : max. 500 pF/500 m.
 
RE-2X(St)YSWAY-fl 
 MP 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Insulation thickness             : 0,50 mm² : 0,40 mm;
                                         0,75 mm² : 0,40 mm;

                                           1,0 mm² : 0,40 mm;

                                           1,3 mm² : 0,45 mm;
                                           1,5 mm² : 0,45 mm.
Conductor resistance           : 0,50 mm² : 36,7 Ω/km;
                                         0,75 mm² : 25,0 Ω/km;
                                       
    1,0 mm² : 18,5 Ω/km;
                                           1,3 mm² : 14,2 Ω/km;

                                           1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)                : 0,50 mm² : 25 µH/Ω;
                                         0,75 mm² : 25 µH/Ω;
                                       
    1,0 mm² : 25 µH/Ω;
                                       
    1,3 mm² : 40 µH/Ω;
                                           1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz)  :      ≤ 4 pairs                        all other pairs

                                        0,50 mm² : max. 115 pF/m,   max. 90 pF/m;
                                      
  0,75 mm² : max. 115 pF/m,   max. 90 pF/m;

                                          1,0 mm² : max. 115 pF/m,   max. 90 pF/m;

                                          1,3 mm² : max. 120 pF/m,  max. 105 pF/m;

                                          1,5 mm² : max. 120 pF/m,  max. 105 pF/m.
 
RE-2X(St)YSWAY-fl 
 MP 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 300 V
 
Standards

Design                  : DIN EN 50288-7.

Conductor             : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation             : EN 50290-2-29.

Armour                 : EN 10257-1.

Inner/Outer sheath : EN 50290-2-22. 

Flame retardancy    : IEC 60332-1 & EN 60332-1.
 
RE-2X(St)YSWAY-fl 
 MP 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.