Categories

RE-2X(St)YSWAY-fl-TIMF
 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC Maximize

RE-2X(St)YSWAY-fl-TIMF
 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC

RE-2X(St)YSWAY-fl-TIMF
 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed instrumentation cable 300 V
 
Construction

Conductor            : plain copper wire, stranded.

Insulation             : XLPE compound, (RE-2X….).
TIMF Construction : polyester tape above the pair, AL-PES tape over solid
                            tinned copper drain wire, 0,60 mm.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Inner/outer sheath : PVC compound, flame retardant/90° C.

Armour                : galvanized round steel wire.
Sheath colour       : RAL 9005, black or RAL 5015, blue.
 
* Please refer to the data sheet for complete information about this cable.

More details

RE-2X(St)YSWAY-fl-TIMF
 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Rated voltage                  : 300 V.

Test voltage                    : Urms core-core   : 1500 V;

                                      Urms core-screen : 1500 V.

Temperature range           : operation   : - 30° C ~ + 90° C;

                                       installation :   - 5° C ~ + 50° C.

Min. bending radius          : 10 x D.

Insulation resistance         : min. 5000 MΩ/km.
 
RE-2X(St)YSWAY-fl-TIMF
 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Insulation thickness          : 0,50 mm² : 0,40 mm;
                                      0,75 mm² : 0,40 mm;

                                        1,0 mm² : 0,40 mm;

                                        1,3 mm² : 0,45 mm;
                                        1,5 mm² : 0,45 mm.
Conductor resistance        : 0,50 mm² : 36,7 Ω/km;

                                      0,75 mm² : 25,0 Ω/km;

                                        1,0 mm² : 18,5 Ω/km;
                                        1,3 mm² : 14,2 Ω/km;

                                        1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)             : 0,50 mm² : 25 µH/Ω;
                                      0,75 mm² : 25 µH/Ω;

                                        1,0 mm² : 25 µH/Ω;

                                        1,3 mm² : 40 µH/Ω;
                                        1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz) : max. 120 pF/m.
 
RE-2X(St)YSWAY-fl-TIMF
 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed instrumentation cable 300 V
 
Standards


Design                 : DIN EN 50288-7.

Conductor            : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation             : EN 50290-2-29.

Armour                : EN 10257-1.

Inner/outer sheath : EN 50290-2-22.

Flame retardancy   : IEC 60332-1 & EN 60332-1.

RE-2X(St)YSWAY-fl-TIMF
 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024