Categories

RE-Yw(St)Yw-fl PIMF 105° C - CU/PVC/ISCR/OSCR/PVC Maximize

RE-Yw(St)Yw-fl PIMF 105° C - CU/PVC/ISCR/OSCR/PVC

RE-Yw(St)Yw-fl PIMF 105° C - CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Construction

Conductor            : plain copper wire, stranded.

Insulation             : PVC compound, 105° C.

Pair                     : two conductors twisted to a pair.
PIMF construction  : polyester tape above the pair, AL-PES tape over solid
                            tinned copper drain wire, 0,60 mm.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper drain
                            wire 0,50 mm².

Outer sheath         : PVC compound, 105° C.

Sheath colour       : RAL 9005, black or RAL 5015, blue.
 
* Please refer to the data sheet for complete information about this cable.

More details

RE-Yw(St)Yw-fl PIMF 105° C - CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Rated voltage                   : 300 V.

Test voltage                     : Urms core-core   : 1500 V;

                                       Urms core-screen : 1500 V.

Temperature range           : operation   : - 30° C ~ + 105° C;

                                      installation :   - 5° C ~ + 50° C.

Min. bending radius         : 7.5 x D.

Insulation resistance        : min. 100 MΩ/km.

Capacitance unbalanced   : (1 kHz) : max. 500 pF/500 m.
 
RE-Yw(St)Yw-fl PIMF 105° C - CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Technical data and tests

Insulation thickness         : 0,50 mm² : 0,40 mm;
                                      0,75 mm² : 0,40 mm;

                                        1,0 mm² : 0,40 mm;

                                        1,3 mm² : 0,45 mm;
                                        1,5 mm² : 0,45 mm.
Conductor resistance        : 0,50 mm² : 36,7 Ω/km;

                                      0,75 mm² : 25,0 Ω/km;

                                        1,0 mm² : 18,5 Ω/km;
                                        1,3 mm² : 14,2 Ω/km;

                                        1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)              : 0,50 mm² : 25 µH/Ω;
                                       0,75 mm² : 25 µH/Ω;
                                     
    1,0 mm² : 25 µH/Ω;

                                         1,3 mm² : 40 µH/Ω;
                                         1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz) : 0,50 mm² : max. 190 pF/m;
                                        0,75 mm² : max. 190 pF/m;
                                          1,0 mm² : max. 190 pF/m;
                                          1,3 mm² : max. 200 pF/m;
                                          1,5 mm² : max. 200 pF/m.
 
RE-Yw(St)Yw-fl PIMF 105° C - CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Standards

Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-21.

Outer sheath       : EN 50290-2-22.

Flame retardancy : IEC 60332-1 & EN 60332-1.
 
RE-Yw(St)Yw-fl PIMF 105° C - CU/PVC/ISCR/OSCR/PVC - Multi-pair, PVC insulated, screened, PVC sheathed instrumentation cable 300 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024