Categories

RE-2X(St)H MP 90° C
 - CU/XLPE/OSCR/LSZH Maximize

RE-2X(St)H MP 90° C
 - CU/XLPE/OSCR/LSZH

RE-2X(St)H MP 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, screened, HFFR sheathed instrumentation cable 500 V 
 
Construction

Conductor             : plain copper wire, stranded.

Insulation              : XLPE compound (RE-2X...).

Core identification  : black / blue cores numbered 1-1, 2-2,…
Upon request         : colour coded according to IEC 60189-2.
Pair                      : two conductors twisted to a pair.
Lay-up                  : pairs laid up in layers of optimum pitch.
Separator              : polyester tape.
Screen                  : AL-PES tape over stranded tinned copper drain
                             wire 0,50 mm².

Outer sheath          : HFFR compound.

Sheath colour        : RAL 9005, black or RAL 5015, blue.
 
*Please check the data sheet for detailed information.

More details

RE-2X(St)H MP 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, screened, HFFR sheathed instrumentation cable 500 V
 
Technical data and tests

Rated voltage            : 500 V.

Test voltage              : Urms core-core   : 2000 V;

                                Urms core-screen : 2000 V.

Temperature range     : operation   : - 30° C ~ + 90° C;

                                installation :   - 5° C ~ + 50° C.

Min. bending radius    : 7.5 x D.

 
RE-2X(St)H MP 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, screened, HFFR sheathed instrumentation cable 500 V
 
Technical data and tests

Insulation resistance   : min. 5000 MΩ/km.
Conductor resistance  : 0,50 mm² : 36,7 Ω/km;
                        
       0,75 mm² : 25,0 Ω/km;
                        
         1,0 mm² : 18,5 Ω/km;
                                 1,3 mm² : 14,2 Ω/km;

                                 1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)      : 0,50 mm² : 25 µH/Ω;
                               0,75 mm² : 25 µH/Ω;

                                 1,0 mm² : 25 µH/Ω;

                                 1,3 mm² : 40 µH/Ω;
                                 1,5 mm² : 40 µH/Ω.

Mutual Capacitance    : ≤ 4 pairs                     all other pairs

                       0,50  mm² : max. 100 pF/m   max. 65 pF/m;
                       0,75  mm² : max. 100 pF/m   max. 65 pF/m; 
                         1,0  mm² : max. 100 pF/m   max. 65 pF/m;
                         1,3  mm² : max. 100 pF/m   max. 75 pF/m;
                         1,5  mm² : max. 100 pF/m   max. 75 pF/m.

Capacitance unbalanced: (1 kHz) : max. 500 pF/500 m.
 
RE-2X(St)H MP 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, screened, HFFR sheathed instrumentation cable 500 V
 
Standards


Design                 : EN 50288-7.

Conductor            : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation             : EN 50290-2-29.

Outer sheath         : EN 50290-2-27.

Flame test             : IEC 60332-1 & DIN EN 60332-1;
                            IEC 60332-3 & DIN EN 50266-2-4
.
Smoke density test : IEC 61034-2 & DIN EN 61034-2
.
Halogen-free test   : IEC 60754-1/2 & DIN EN 50267-2.
 
RE-2X(St)H MP 90° C
 - CU/XLPE/OSCR/LSZH - XLPE insulated, screened, HFFR sheathed instrumentation cable 500 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables are used in environments which must have no corrosive gases emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024