RE-2X(St)HSWAH MP 90° C - CU/XLPE/OSCR/LSZH/SWA/LSZH - XLPE insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V Technical data and tests
Rated voltage : 500 V.Test voltage : Urms core-core : 2000 V; Urms core-screen : 2000 V.Temperature range : operation : - 30° C ~ + 90° C; installation : - 5° C ~ + 50° C.Min. bending radius : 10 x D
RE-2X(St)HSWAH MP 90° C - CU/XLPE/OSCR/LSZH/SWA/LSZH - XLPE insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V
Technical data and tests
Conductor resistance : 0,50 mm² : 36,7 Ω/km;
0,75 mm² : 25,0 Ω/km;
1,0 mm² : 18,5 Ω/km;
1,3 mm² : 14,2 Ω/km;
1,5 mm² : 12,3 Ω/km.
Insulation resistance : min. 5000 MΩ/km.
Mutual capacitance : ≤ 4 pairs all other pairs
0,50 mm² : max. 100 pF/m max. 65 pF/m;
0,75 mm² : max. 100 pF/m max. 65 pF/m;
1,0 mm² : max. 100 pF/m max. 65 pF/m;
1,3 mm² : max. 100 pF/m max. 75 pF/m;
1,5 mm² : max. 100 pF/m max. 75 pF/m.
Capacitance unbalanced : (1 kHz) : max. 500 pF/500 m.
L / R (ratio) (max.) : 0,50 mm² : 25 µH/Ω;
0,75 mm² : 25 µH/Ω;
1,0 mm² : 25 µH/Ω;
1,3 mm² : 40 µH/Ω;
1,5 mm² : 40 µH/Ω.
RE-2X(St)HSWAH MP 90° C - CU/XLPE/OSCR/LSZH/SWA/LSZH - XLPE insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V
Standards
Design : EN 50288-7.
Conductor : IEC 60228 class 2, DIN EN 60228 class 2.
Insulation : EN 50290-2-29.
Inner sheath : EN 50290-2-27.
Armour : EN 10257-1.
Outer sheath : EN 50290-2-27.
Flame test : IEC 60332-1 & DIN EN 60332-1;
IEC 60332-3 & DIN EN 50266-2-4.
Smoke density : IEC 61034-2 & DIN EN 61034-2.
Halogen-free : IEC 60754-1/2 & DIN EN 50267-2.
RE-2X(St)HSWAH MP 90° C - CU/XLPE/OSCR/LSZH/SWA/LSZH - XLPE insulated, screened, armoured, HFFR sheathed instrumentation cable 500 V Applications
These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... These cables are used in environments which must have no corrosive gases emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These cables are recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.