RE-Yw(St)YwSWAYw-fl 
105° C - CU/PVC/OSCR/PVC Maximize

RE-Yw(St)YwSWAYw-fl 
105° C - CU/PVC/OSCR/PVC

RE-Yw(St)YwSWAYw-fl 
105° C - CU/PVC/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation and control cable 500 V
 
Construction
 
Conductor           : plain copper wire, stranded.

Insulation            : PVC compound, 105° C
.
Core identification : black cores are numbered 1-2-3... Other core
                            configurations upon request.
Lay-up                 : cores laid up in layers of optimum pitch.
Separator             : polyester tape.

Inner sheath         : PVC compound, 105° C.

Armour                : galvanized round steel wire.
Screen                 : AL-PES tape over stranded tinned copper drain
                            wire 0,50 mm².

Outer sheath        : PVC compound, 105° C
.
Sheath colour      : RAL 9005, black or RAL 5015, blue.

More details

RE-Yw(St)YwSWAYw-fl 
105° C - CU/PVC/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation and control cable 500 V
 
Technical data and tests

Rated voltage           : 500 V.

Test voltage             : Urms core-core    : 2000 V;

                               Urms core-screen : 2000 V.

Temperature range    : operation   : - 30° C ~ + 105° C;

                               installation :   - 5° C ~ + 50° C.

Min. bending radius  : 10 x D.

Insulation resistance : min. 100 MΩ/km.

Mutual capacitance   : (1 kHz) : max. 190 pF/m.
 
RE-Yw(St)YwSWAYw-fl 
105° C - CU/PVC/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation and control cable 500 V
 
Technical data and tests

Conductor resistance  : 0,50 mm² : 36,0 Ω/km;

                                0,75 mm² : 24,5 Ω/km;

                                  1,0 mm² : 18,1 Ω/km;
                                  1,3 mm² : 13,9 Ω/km;

                                  1,5 mm² : 12,1 Ω/km;

                                  2,5 mm² :   7,4 Ω/km.

L/R (ratio) (max)       : 0,50 mm² : 25 µH/Ω;
                                0,75 mm² : 25 µH/Ω;

                                  1,0 mm² : 25 µH/Ω;

                                  1,3 mm² : 40 µH/Ω;
                                  1,5 mm² : 40 µH/Ω;

                                  2,5 mm² : 60 µH/Ω.
 
RE-Yw(St)YwSWAYw-fl instrumentation and control cable 500 V - Standards
Design          : DIN EN 50288-7.

Conductor     : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation      : EN 50290-2-21.

Inner sheath  : EN 50290-2-22.

Armour         : EN 10257-1.

Outer sheath : EN 50290-2-27. 

Flame test     : IEC 60332-1 & DIN EN 60332-1.

                    IEC 60332-3 & DIN EN 50266-2-4.
 
RE-Yw(St)YwSWAYw-fl instrumentation and control cable 500 V - Applications
These cables are used for control purposes (e.g. controlling of pumps, valves or engines) at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed to be directly connected to a low impedance source, e.g. public mains electricity supply.
With blue sheath they are suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.