RE-2X(St)Y-fl 90° C  -  CU/XLPE/OSCR/PVC Maximize

RE-2X(St)Y-fl 90° C - CU/XLPE/OSCR/PVC

RE-2X(St)Y-fl 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V
 
Construction

Conductor            : plain copper wire, stranded.

Insulation             : XLPE compound (RE-2X...).

Core identification : black / blue / red cores numbered 1-1, 2-2,…
Upon request        : colour coded according to IEC 60189-2.

Triple                   : three conductors twisted to a triple.
Lay-up                 : triples laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper
                            drain wire 0,50 mm².

Outer sheath         : PVC compound, 90° C.

Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2X(St)Y-fl 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V
 
Technical data and tests

Rated voltage           : 500 V. 

Test voltage             : Urms core-core   : 2000 V;

                               Urms core-screen : 2000 V.

Temperature range    : operation   : - 30° C ~ + 90° C;
                             
  installation :   - 5° C ~ + 50° C.

Min. bending radius  : 7.5 x D.

Insulation resistance : min. 5000 MΩ/km.
 

RE-2X(St)Y-fl 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V

Technical data and tests



Conductor resistance        : 0,50 mm² : 36,7 Ω/km;
                                    
  0,75 mm² : 25,0 Ω/km;

                                        1,0 mm² : 18,5 Ω/km;
                                        1,3 mm² : 14,2 Ω/km;

                                        1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)             : 0,50 mm² : 25 µH/Ω;
                                      0,75 mm² : 25 µH/Ω;

                                        1,0 mm² : 25 µH/Ω;

                                        1,3 mm² : 40 µH/Ω;
                                        1,5 mm² : 40 µH/Ω.

Mutual capacitance (1 kHz) : max 100 pF/m.

RE-2X(St)Y-fl 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V

Standards

Design               : DIN EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-29.

Outer sheath       : EN 50290-2-22. 

Flame retardancy : IEC 60332-1 & EN 60332-1.

RE-2X(St)Y-fl 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.