RE-2X(St)Y-fl MP
90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V Technical data and tests
Rated voltage : 500 V.
Test voltage : Urms core-core : 2000 V;
Urms core-screen : 2000 V.
Temperature range : operation : - 30° C ~ + 90° C;
installation : - 5° C ~ + 50° C.
Min. bending radius : 7.5 x D.
Insulation resistance : min. 5000 MΩ/km.
RE-2X(St)Y-fl MP 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V
Technical data and tests
Conductor resistance : 0,50 mm² : 36,7 Ω/km;
0,75 mm² : 25,0 Ω/km;
1,0 mm² : 18,5 Ω/km;
1,3 mm² : 14,2 Ω/km;
1,5 mm² : 12,3 Ω/km.
L/R (ratio) (max) : 0,50 mm² : 25 µH/Ω;
0,75 mm² : 25 µH/Ω;
1,0 mm² : 25 µH/Ω;
1,3 mm² : 40 µH/Ω;
1,5 mm² : 40 µH/Ω.
Insulation thickness : 0,50 mm² : 0,40 mm;
0,75 mm² : 0,40 mm;
1,0 mm² : 0,40 mm;
1,3 mm² : 0,45 mm;
1,5 mm² : 0,45 mm.
Mutual capacitance : ≤ 4 pairs all other pairs
0,50 mm² : max. 100 pF/m, max. 65 pF/m;
0,75 mm² : max. 100 pF/m, max. 65 pF/m;
1,0 mm² : max. 100 pF/m, max. 65 pF/m;
1,3 mm² : max. 100 pF/m, max. 75 pF/m;
1,5 mm² : max. 100 pF/m, max. 75 pF/m.
RE-2X(St)Y-fl MP 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V
Standards
Design : DIN EN 50288-7.
Conductor : IEC 60228 class 2, DIN EN 60228 class 2.
Insulation : EN 50290-2-29.
Outer sheath : EN 50290-2-22.
Flame retardancy : IEC 60332-1 & EN 60332-1.
RE-2X(St)Y-fl MP 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation cable 500 V Applications
These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.