Categories

RE-2X(St)Y 90° C - CU/XLPE/OSCR/PVC Maximize

RE-2X(St)Y 90° C - CU/XLPE/OSCR/PVC

RE-2X(St)Y 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation and control cable 500 V
 
Construction
 

Conductor            : stranded copper wires, class 2.

Insulation             : XLPE compound (RE-2X...).
Core identification : black cores numbered 1-2-3...

Lay-up                 : cores laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper
                            drain wire 0,50 mm².

Outer sheath         : PVC compound, 90° C.
Sheath colour       : RAL 9005, black or RAL 5015, blue.
Note : other core configurations manufactured upon request.

More details

RE-2X(St)Y 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation and control cable 500 V
 

Technical data and tests

Rated voltage         : 500 V.
Test voltage           : Urms core-core    : 2000 V;

                             Urms core-screen : 2000 V.
Temperature range  : operation   : - 30° C ~ + 90° C;
                             installation :   - 5° C ~ + 50° C.
Min. bending radius : 7.5 x D.
 
RE-2X(St)Y 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation and control cable 500 V
 
Technical data and tests


Conductor resistance (20° C): 0,50 mm² : 36,7 Ω/km;
                                         0,75 mm² : 24,5 Ω/km;
                                           1,0 mm² : 18,1 Ω/km;
                                           1,3 mm² : 13,9 Ω/km;
                                           1,5 mm² : 12,1 Ω/km;

                                           2,5 mm² :   7,4 Ω/km.
L / R (ratio) (max.)              : 0,50 mm² : 25 µH/Ω;
                                          0,75 mm² : 25 µH/Ω;
                                            1,0 mm² : 25 µH/Ω;
                                            1,3 mm² : 40 µH/Ω;

                                            1,5 mm² : 40 µH/Ω;

                                            2,5 mm² : 60 µH/Ω.
Insulation resistance (20° C)  : min. 5000 MΩ/km.

Mutual capacitance               : max. 120 pF/m (1 kHz).
 
RE-2X(St)Y 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation and control cable 500 V

Standards

Design                : EN 50288-7.

Conductor           : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation            : EN 50290-2-29.
Outer sheath        : EN 50290-2-22.
Flame test            : IEC 60332-1 & DIN EN 60332-1.
                           IEC 60332-3 & DIN EN 50266-2-4.

RE-2X(St)Y 90° C - CU/XLPE/OSCR/PVC - XLPE insulated, collective screened, PVC sheathed instrumentation and control cable 500 V

Applications


These cables are used for control purposes (e.g. controlling of pumps, valves or engines) at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed to be directly connected to a low impedance source, e.g. public mains electricity supply.
With blue sheath they are suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.