RE-2X(St)YSWAY-fl 90° C - CU/XLPE/OSCR/PVC/SWA/PVC

RE-2X(St)YSWAY-fl 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, screened, PVC sheathed instrumentation cable 500 V
 
Construction

Conductor            : stranded copper wires, class 2.

Insulation             : XLPE compound (RE-2X..)
Lay-up                 : cores laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : AL-PES tape over stranded tinned copper
                            drain wire 0,50 mm².

Inner sheath         : PVC compound, 90° C.

Armour                : galvanized round steel wire.

Outer sheath         : PVC compound, 90° C.

Sheath colour       : RAL 9005, black or RAL 5015, blue.
Core identification : black cores numbered 1-2-3...


More details

RE-2X(St)YSWAY-fl 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, screened, PVC sheathed instrumentation cable 500 V
 
Technical data and tests


Rated voltage          : 500 V.
Test voltage            : Urms core-core    : 2000 V;

                              Urms core-screen : 2000 V.
Temp. range           : operation   : - 30° C ~ + 90° C;
                              installation :   - 5° C ~ + 50° C.

Min. bending radius : 10 x D.
 
RE-2X(St)YSWAY-fl 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, screened, PVC sheathed instrumentation cable 500 V

Technical data and tests


Conductor resistance (20° C) : 0,50 mm² : 36,7 Ω/km;
                                          0,75 mm² : 24,5 Ω/km;
                                            1,0 mm² : 18,1 Ω/km;
                                            1,3 mm² : 13,9 Ω/km;
                                            1,5 mm² : 12,1 Ω/km;

                                            2,5 mm² :   7,4 Ω/km.
L / R (ratio) (max.)               : 0,50 mm² : 25 µH/Ω;
                                           0,75 mm² : 25 µH/Ω;
                                             1,0 mm² : 25 µH/Ω;
                                             1,3 mm² : 40 µH/Ω; 

                                             1,5 mm² : 40 µH/Ω;

                                             2,5 mm² : 60 µH/Ω;
Insulation resistance (20° C)  : min. 5000 MΩ/km.

Mutual capacitance               : max. 120 pF/m (1 kHz).
 
RE-2X(St)YSWAY-fl 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, screened, PVC sheathed instrumentation cable 500 V

Standards


Design                 : EN 50288-7.

Conductor            : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation             : EN 50290-2-29.

Inner sheath         : EN 50290-2-22.
Armour                : EN 10257-1.

Outer sheath         : EN 50290-2-22.
Flame test            : IEC 60332-1 & DIN EN 60332-1.
                           IEC 60332-3 & DIN EN 50266-2-4.
 
RE-2X(St)YSWAY-fl 90° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, screened, PVC sheathed instrumentation cable 500 V
 
Applications

These cables are used for control purposes (e.g. controlling of pumps, valves or engines) at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed to be directly connected to a low impedance source, e.g. public mains electricity supply.
With blue sheath they are suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.