Categories

RE-Yw(St)YwSWAYw-fl-TIMF 105° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC
 Maximize

RE-Yw(St)YwSWAYw-fl-TIMF 105° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC


RE-Yw(St)YwSWAYw-fl-TIMF 105° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC
 - PVC sheathed, screened, armoured instrumentation cable 500 V
 
Construction

Conductor           : plain copper wire, stranded.

Insulation            : PVC compound, 105° C.
TIMF construction : polyester tape above the triple, AL-PES tape over
                           solid tinned copper drain wire, 0,60 mm.
Separator            : polyester tape.
Screen                : AL-PES tape over stranded tinned copper drain
                          wire 0,50 mm².

Inner sheath        : PVC compound 105° C.

Armour               : galvanized round steel wire.

Outer sheath        : PVC compound, 105° C.
Sheath colour      : RAL 9005, black or RAL 5015, blue.

*Please check the data sheet for detailed information.
 

More details

RE-Yw(St)YwSWAYw-fl-TIMF 105° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC
 - PVC sheathed, screened, armoured instrumentation cable 500 V
 
Technical data and tests

Rated voltage         : 500 V.

Test voltage           : Urms core-core    : 2000 V;

                             Urms core-screen : 2000 V.
Temperature range : operation   : - 30° C ~ + 105° C;
                             installation :  - 5° C ~ + 50° C.
Min. bending radius : 10 x D.

Insulation resistance : min. 100 MΩ/km.
 
RE-Yw(St)YwSWAYw-fl-TIMF 105° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC
 - PVC sheathed, screened, armoured instrumentation cable 500 V

Technical data and tests

Conductor resistance : 0,50 mm² : 36,7 Ω/km;

                                 0,75 mm² : 25,0 Ω/km;

                                   1,0 mm² : 18,5 Ω/km;

                                   1,3 mm² : 14,2 Ω/km;

                                   1,5 mm² : 12,3 Ω/km
Insulation resistance   : min. 100 MΩ/km.
Mutual Capacitance   : 0,50  mm² : max. 160 pF/m;

                                 0,75  mm² : max. 160 pF/m;

                                   1,0  mm² : max. 160 pF/m;

                                   1,3  mm² : max. 170 pF/m;

                                   1,5  mm² : max. 170 pF/m
L / R (ratio) (max.)    : 0,50 mm² : 25 µH/Ω;

                                 0,75 mm² : 25 µH/Ω;

                                   1,0 mm² : 25 µH/Ω;

                                   1,3 mm² : 40 µH/Ω; 

                                   1,5 mm² : 40 µH/Ω.
 
RE-Yw(St)YwSWAYw-fl-TIMF 105° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC
 - PVC sheathed, screened, armoured instrumentation cable 500 V
 
Standards


Design               : EN 50288-7.

Conductor          : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation           : EN 50290-2-21.

Inner sheath       : EN 50290-2-22.

Armour              : EN 10257-1.

Outer sheath       : EN 50290-2-22.

Flame retardance : IEC 60332-1 & EN 60332-1.
 
RE-Yw(St)YwSWAYw-fl-TIMF 105° C - CU/PVC/ISCR/OSCR/PVC/SWA/PVC
 - PVC sheathed, screened, armoured instrumentation cable 500 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed to be directly connected to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024