RE-2X(St)YSWAY-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V Technical Data and Tests
Rated voltage : 500 V.
Test voltage : Urms core-core : 2000 V;
Urms core-screen : 2000 V.
Temperature range : operation : - 30° C ~ + 90° C; installation : - 5° C ~ + 50° C.Min. bending radius : 10 x D.
Capacitance unbalanced : (1 kHz) : max. 500 pF/500 m.
RE-2X(St)YSWAY-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V
Technical data and tests
Conductor resistance (20° C) : 0,50 mm² : 36,7 Ω/km;
0,75 mm² : 25,0 Ω/km;
1,0 mm² : 18,5 Ω/km;
1,3 mm² : 14,2 Ω/km;
1,5 mm² : 12,3 Ω/km.
Insulation resistance (20° C) : min. 5000 MΩ/km.
Mutual capacitance (1 kHz) : ≤ 4 pairs all other pairs
0,50 mm² : max. 100 pF/m, max. 65 pF/m;
0,75 mm² : max. 100 pF/m, max. 65 pF/m;
1,0 mm² : max. 100 pF/m, max. 65 pF/m;
1,3 mm² : max. 100 pF/m, max. 75 pF/m;
1,5 mm² : max. 100 pF/m, max. 75 pF/m.
L/R (ratio) (max) : 0,50 mm² : 25 µH/Ω;
0,75 mm² : 25 µH/Ω;
1,0 mm² : 25 µH/Ω;
1,3 mm² : 40 µH/Ω;
1,5 mm² : 40 µH/Ω.
RE-2X(St)YSWAY-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V
Standards Design : DIN EN 50288-7.
Conductor : IEC 60228 class 2, DIN EN 60228 class 2.
Insulation : EN 50290-2-29.
Inner/Outer sheath : EN 50290-2-22.
Armour : EN 10257-1.
Flame retardancy test : IEC 60332-1 & EN 60332-1. RE-2X(St)YSWAY-fl-PIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V Applications
These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. The armour above the inner sheath protects the cable from mechanical shocks. These cables are recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.