RE-Yw(St)Yw-fl 90° C - CU/PVC/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 600 V
 
Construction
 
Conductor            : stranded plain annealed copper, 1,30mm²: 7x0,488 mm.

Insulation             : PVC compound, 90° C.

Core identification : black and white coloured.

Lay-up                 : cores twisted together.
Separator             : polyester tape.
Screen                 : AL-PES tape 7x0,30 mm over stranded tinned copper
                            drain wire.

Outer sheath        : PVC compound, 90° C, flame retardant, UV resistant.

More details

RE-Yw(St)Yw-fl 90° C - CU/PVC/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 600 V
 
Technical data and tests

Rated voltage                      : 600 V. 

Test voltage (AC 50 Hz)       : 2500 V.
Temperature range              : -30° C ~ +90° C.

Nominal capacitance (1 kHz) : max. 150 nF/km.
Inductance                           : max. 1 mH/km.

Insulation resistance             : min. 100 MΩ/km.

Min. bending radius              : 10 x D.
 
RE-Yw(St)Yw-fl 90° C - CU/PVC/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 600 V

Standards

Design               : UL 1277, ANSI/ICEA S-73-532 NEMA WC 57 
  (ICEA S-82-552 is old version).

Cond. resistance : ICEA S-73-532 (at 25° C).

Flame test          : IEC 60332-1 , UL 1581.

                           IEC 60332-3-24 CAT C, IEEE -383.
Oil resistance      : ICEA S-73-532.
 
RE-Yw(St)Yw-fl 90° C - CU/PVC/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 600 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.