Categories

RE-Yw(St)Yw-fl PIMF 90° C - CU/PVC/ISCR/OSCR/PVC Maximize

RE-Yw(St)Yw-fl PIMF 90° C - CU/PVC/ISCR/OSCR/PVC

RE-Yw(St)Yw-fl PIMF 90° C - CU/PVC/ISCR/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 600 V
 
Construction
 
Conductor       : stranded plain annealed copper, 1,30mm²: 7x0,488 mm.

Insulation       : PVC compound, 90° C.


Pair               : two cores twisted to pair; pair identification with numbered
                       tape 1,2,3...

Pair separator : polyester tape.

Pair screen     : aluminium polyester tape with 7x0,30 mm tinned copper
                          drain wire.

Pair separator : polyester tape with numbered tape.

Separator       : polyester tape.
Screen            : AL-PES tape over stranded tinned copper
                        drain wire.

Outer sheath   : PVC compound, 90° C, flame retardant, UV resistant.
 
*Complete information in the data sheet.

More details

RE-Yw(St)Yw-fl PIMF 90° C - CU/PVC/ISCR/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 600 V
 
Technical data and tests

Rated voltage                      : 600 V. 

Test voltage (AC 50 Hz)       : 2500 V.
Temperature range              : -30° C ~ +90° C.

Nominal capacitance (1 kHz) : max. 150 nF/km.
Inductance                           : max. 1 mH/km.

Insulation resistance             : min. 100 MΩ/km.

Min. bending radius              : 10 x D.
 
RE-Yw(St)Yw-fl PIMF 90° C - CU/PVC/ISCR/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 600 V

Standards

Design               : UL 1277, ANSI/ICEA S-73-532 NEMA WC 57 
  (ICEA S-82-552 is old version).

Cond. resistance : ICEA S-73-532 (at 25° C).

Flame test          : IEC 60332-1 , UL 1581.

                           IEC 60332-3-24 CAT C, IEEE -383.
Oil resistance      : ICEA S-73-532.
 
RE-Yw(St)Yw-fl PIMF 90° C - CU/PVC/ISCR/OSCR/PVC - PVC insulated, screened, PVC sheathed instrumentation cable 600 V
 
Applications


These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
These cables are not recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024