Categories

RE-2X(St)YSWAY-fl-TIMF   90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC Maximize

RE-2X(St)YSWAY-fl-TIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC

RE-2X(St)YSWAY-fl-TIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed cable 500 V
 
Construction

Conductor             : plain copper wire, stranded.

Insulation             : XLPE compound, (RE-2X….).

TIMF construction : polyester tape above the pair, AL-PES tape
                              over solid tinned copper drain wire, 0,60 mm.
Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain
                             wire 0,50 mm².

Inner sheath         : PVC compound 90° C.
Armour                 : galvanized round steel wire.

Outer sheath         : PVC compound, 90° C.
Sheath colour        : RAL 9005, black or RAL 5015, blue.
 
*Please check the data sheet for detailed information.

More details

RE-2X(St)YSWAY-fl-TIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed cable 500 V
 
Technical data and tests

Rated voltage         : 500 V.

Test voltage           : Urms core-core    : 2000 V;
                             
  Urms core-screen : 2000 V.

Temperature range : operation : - 30° C ~ + 90° C;
                               installation : - 5° C ~ + 50° C.
Min. bending radius : 10 x D.
 
RE-2X(St)YSWAY-fl-TIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed cable 500 V

Technical data and tests

Conductor resistance (20° C) : 0,50 mm² : 36,7 Ω/km;
                                           
  0,75 mm² : 25,0 Ω/km;
                                           
    1,0 mm² : 18,5 Ω/km;  
                                               1,3 mm² : 14,2 Ω/km;
                                           
    1,5 mm² : 12,3 Ω/km.

Insulation resistance (20° C)   : min. 5000 MΩ/km.

Mutual capacitance (1 kHz)     : max. 100 pF/m.

L/R (ratio) (max)                   : 0,50 mm² : 25 µH/Ω;
                                            
  0,75 mm² : 25 µH/Ω;
                                            
    1,0 mm² : 25 µH/Ω;

                                                1,3 mm² : 40 µH/Ω;  
                                            
    1,5 mm² : 40 µH/Ω.
 
RE-2X(St)YSWAY-fl-TIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed cable 500 V
 
Standards

Design                      : DIN EN 50288-7. 

Conductor                 : IEC 60228 class 2,
                                
  DIN EN 60228 class 2.

Insulation                  : EN 50290-2-29.

Inner/Outer sheath     : EN 50290-2-22.

Armour                      : EN 10257-1.

Flame retardancy test : IEC 60332-1 & EN 60332-1.
 
RE-2X(St)YSWAY-fl-TIMF 90° C - CU/XLPE/ISCR/OSCR/PVC/SWA/PVC - XLPE insulated, screened, armoured, PVC sheathed cable 500 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.