Categories

RE-2X(St)HSWAH-TIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH/SWA/LSZH
 Maximize

RE-2X(St)HSWAH-TIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH/SWA/LSZH


RE-2X(St)HSWAH-TIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, 
screened, armoured, LSZH sheathed cable 300/500 V
 
Construction

Conductor            : plain annealed copper wire.

Insulation             : XLPE compound.
Core ident.           : black/white/red; with numbered tape under separator
                             tape of the pair screen.
TIMF construction : polyester tape above the pair, AL-PES tape over tinned
                             copper drain wire.
Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain wire 0,50 mm².

Bedding               : LSZH compound, black.

Armour                : galvanized round steel wire.

Outer sheath        : LSZH compound, LST1.
Sheath colour       : RAL 9005, black or RAL 5015, blue.

More details

RE-2X(St)HSWAH-TIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, 
screened, armoured, LSZH sheathed cable 300/500 V

Technical data and tests

Rated voltage (Uo/U)     : 300/500 V.

Test voltage                  : Urms core-core : 1000 V;
                                    
  Urms core-screen : 1000 V.

Temperature range        : operation : - 40° C ~ + 90° C;
                                    
  installation : - 5° C ~ + 50° C.

Capacitance unbalanced  : (1 kHz) : max. 250 pF/250 m.

Insulation resistance       : min. 5000 MΩ/km.

Min. bending radius        : 8 x D.

L/R (ratio) (max)           : 0,50 mm² : 25 µH/Ω;
                                    
  0,75 mm² : 25 µH/Ω;

                                        1,0 mm² : 25 µH/Ω;

                                        1,5 mm² : 40 µH/Ω.
 
RE-2X(St)HSWAH-TIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, 
screened, armoured, LSZH sheathed cable 300/500 V

Technical data and tests


Insulation thickness          : 0,50 mm² : 0,50 mm;
                                          1,0 mm² : 0,60 mm;

                                         0,50 mm² : 0,60 mm;
                                         0,75 mm² : 0,60 mm;
                                         1,50 mm² : 0,60 mm.

Conductor class, BS 6360   : 0,50 mm² : Class 1;

                                           1,0 mm² : Class 1;

                                         0,50 mm² : Class 5;
                                         0,75 mm² : Class 5;
                                         1,50 mm² : Class 2.

Conductor resistance         : 0,50 mm² : 36,8 Ω/km;

                                           1,0 mm² : 18,4 Ω/km;
                                         0,50 mm² : 39,7 Ω/km;
                                         0,75 mm² : 26,5 Ω/km;
                                         1,50 mm² : 12,3 Ω/km.
 
Mutual capacitance (1 kHz) :      ≤2 pairs                  all other pairs
                                 0,50  mm² : max. 115 pF/m,  max. 75 pF/m;
                                 0,75  mm² : max. 115 pF/m,  max. 75 pF/m;
                                    1,0 mm² : max. 115 pF/m,  max. 75 pF/m;
                          
          1,5 mm² : max. 120 pF/m,  max. 85 pF/m.
 
RE-2X(St)HSWAH-TIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, 
screened, armoured, LSZH sheathed cable 300/500 V
 
Standards
 

Design                   : BS 5308 Part 1 Type 1.

Conductor              : BS 6360.

Insulation               : BS 7655.

Armour                   : BS EN 10257-1.

Outer sheath           : BS 7655.

Flame retardancy    : IEC 60332-1 & BS EN 60332-1.
                              
  IEC 60332-3 & BS EN 50266-2-4.

Smoke density         : IEC 61034-2 & BS EN 61034-2.

Halogen-free           : IEC 60754-1/2 & BS EN 50267-2.
 
RE-2X(St)HSWAH-TIMF 90° C - CU/XLPE/ISCR/OSCR/LSZH/SWA/LSZH
 - XLPE insulated, 
screened, armoured, LSZH sheathed cable 300/500 V

Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low.
No corrosive gases are emitted in the event of fire. With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and oudoor installation, in dry and wet locations; on racks, trays, in conduits.

All Rights Reserved Halley Cables © 2006 - 2024