RE-2X(St)YSWAYÖ-uv-fl MP 70° C - CU/XLPE/OSCR/PVC/SWA/PVC Maximize

RE-2X(St)YSWAYÖ-uv-fl MP 70° C - CU/XLPE/OSCR/PVC/SWA/PVC

RE-2X(St)YSWAYÖ-uv-fl MP 70° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V
 
Construction

Conductor           : plain copper wire, stranded.

Insulation            : XLPE compound, (RE-2X….).

Core identification : black / white cores numbered 1-1, 2-2,…

Pair                     : two conductors twisted to a pair.

Lay-up                : pairs laid up in layers of optimum pitch.

Separator             : polyester tape.

Screen                 : AL-PES tape over tinned copper drain
                            wire 0,50 mm².

Inner sheath         : PVC compound.

Armour                : galvanized round steel wire.

Outer sheath         : PVC compound, UV and oil resistant.
Sheath colour       : RAL 9005, grey or RAL 5015, blue.

More details

RE-2X(St)YSWAYÖ-uv-fl MP 70° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V
 
Technical data and tests

Rated voltage               : 500 V.

Test voltage                 : Urms core-core    : 2000 V; 

                                     Urms core-screen : 2000 V.

Temperature range        : operation : - 30° C ~ + 70° C;
                                      installation : - 5° C ~ + 50° C.
Min. bending radius       : 10 x D.

Capacitance unbalanced : (1 kHz) : max. 500 pF/500 m.
 
RE-2X(St)YSWAYÖ-uv-fl MP 70° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V
 
Technical data and tests
 

Conductor resistance (20° C) : 0,50 mm² : 36,7 Ω/km;
                                           
  0,75 mm² : 25,0 Ω/km;
                                           
    1,0 mm² : 18,5 Ω/km;  
                                               1,3 mm² : 14,2 Ω/km;
                               
                1,5 mm² : 12,3 Ω/km.
 
Insulation resistance (20° C) : min. 5000 MΩ/km
.
Mutual capacitance (1 kHz) :   ≤ 4 pairs                all other pairs

                              0,50 mm² : max. 100 pF/m,  max. 65 pF/m;
                              0,75 mm² : max. 100 pF/m,  max. 65 pF/m;
                                1,0 mm² : max. 100 pF/m,  max. 65 pF/m;
                                1,3 mm² : max. 100 pF/m,  max. 75 pF/m;
                                1,5 mm² : max. 100 pF/m,  max. 75 pF/m.

L/R (ratio) (max)              : 0,50 mm² : 25 µH/Ω;

                                       0,75 mm² : 25 µH/Ω;

                                         1,0 mm² : 25 µH/Ω;

                                         1,3 mm² : 40 µH/Ω;
                                     
    1,5 mm² : 40 µH/Ω.
 
RE-2X(St)YSWAYÖ-uv-fl MP 70° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V
 
Standards
 
Standard                   : DIN EN 50288-7.

Conductor                 : IEC 60228 class 2, DIN EN 60228 class 2.

Insulation                  : EN 50290-2-29.

Inner sheath              : EN 50290-2-22.

Armour                      : EN 10257-1.

Flame retardancy test : IEC 60332-1 & EN 60332-1.
Sunlight resistancec     : UL 1581 section 1200.
Oil resistance              : ICEA S-82-552.
 
RE-2X(St)YSWAYÖ-uv-fl MP 70° C - CU/XLPE/OSCR/PVC/SWA/PVC - XLPE insulated, armoured, PVC sheathed instrumentation cable 500 V
 
Applications

These cables are used for transmission of analogue and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroleum plants, etc... .
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.