RE-m2X(St)HSWAH-CI PIMF FE 180   90° C
 - CU/mc/XLPE/ISCR/OSCR/LSZH/SWA/LSZH Maximize

RE-m2X(St)HSWAH-CI PIMF FE 180 90° C
 - CU/mc/XLPE/ISCR/OSCR/LSZH/SWA/LSZH

RE-m2X(St)HSWAH-CI PIMF FE 180   90° C
 - CU/mc/XLPE/ISCR/OSCR/LSZH/SWA/LSZH - XLPE  insulated, collective screened, armoured, HFFR sheathed cable 500 V
 
Construction
 
Conductor    : plain annealed copper wire, stranded.

Separator     : mica tape.

Insulation     : XLPE compound.
PIMF constr.  : polyester tape above the pair, AL-PES tape over solid tinned
                    copper drain wire, 0,60 mm.
Separator      : polyester tape.
Screen          : AL-PES (aluminium polyester) tape over stranded tinned
                     copper drain wire (7x0,30 mm) 0,50 mm².

Inner sheath  : HFFR (LSZH) compound.

Armour         : galvanized round steel wires.

Outer sheath  : HFFR (LSZH) compound, oil resistant, hydrocarbon resistant,
                     UV resistant, sunlight resistant.


More details

RE-m2X(St)HSWAH-CI PIMF FE 180   90° C
 - CU/mc/XLPE/ISCR/OSCR/LSZH/SWA/LSZH  - XLPE  insulated, collective screened, armoured, HFFR sheathed cable 500 V
 
Technical data and tests
 

Rated voltage              : 500 V. 

Test voltage                : Urms core-core    : 2000 V;
                                
   Urms core-screen : 2000 V.

Temperature range       : operation   : - 30° C ~ + 90° C
                                
  installation :   - 5° C ~ + 50° C.

Min. bending radius      : 10 x D.

Insulation resistance      : min. 5000 MΩ/km.

Capacitance unbalanced : max. 500 pF/500 m (1 kHz).

Inductance                  : max. 1 mH/km (1 kHz).

RE-m2X(St)HSWAH-CI PIMF FE 180   90° C
 - CU/mc/XLPE/ISCR/OSCR/LSZH/SWA/LSZH - XLPE  insulated, collective screened, armoured, HFFR sheathed cable 500 V
 
Technical data and tests


Conductor resistance   :      0,50 mm² : 36,7 Ω/km;
                                    
  0,75 mm² : 25,0 Ω/km;
                                    
    1,0 mm² : 18,5 Ω/km;
                                        1,3 mm² : 14,2 Ω/km;
                                    
    1,5 mm² : 12,3 Ω/km.

L/R (ratio) (max)              : 0,50 mm² : 25 µH/Ω;
                                       0,75 mm² : 25 µH/Ω;

                                         1,0 mm² : 25 µH/Ω;
                                     
    1,3 mm² : 40 µH/Ω;
                                         1,5 mm² : 40 µH/Ω.

Mutual Capacitance (1 kHz)  :  ≤ 4 pairs                      all other pairs

                                    0,50 mm² : max. 100 pF/m;   max. 65 pF/m;

                                    0,75 mm² : max. 100 pF/m;   max. 65 pF/m;
                                
     1,0  mm² : max. 100 pF/m;   max. 65 pF/m;
                                
     1,3  mm² : max. 100 pF/m;   max. 75 pF/m;
                                     1,5  mm² : max. 100 pF/m.   max. 75 pF/m.  
 
RE-m2X(St)HSWAH-CI PIMF FE 180   90° C
 - CU/mc/XLPE/ISCR/OSCR/LSZH/SWA/LSZH - XLPE  insulated, collective screened, armoured, HFFR sheathed cable 500 V

Standards

Design                             : DIN EN 50288-7.

Conductor                        : DIN EN 60228 class 2.

Insulation                         : EN 50290-2-29.

Inner/Outer sheath             : EN 50290-2-27.

Armour                             : EN 10257-1.

Flame test                         : single cable  : IEC 60332-1-2.

                                         bunched      : IEC 60332-3-24 (Cat. C).

Amount of halogen acid gas : IEC 60754-1 (0%).

Degree of acidity of gases    : IEC 60754-2 (ph>4.3; C<10 µS/mm).

Circuit integrity                  : IEC 60331-21.

Smoke density                   : IEC 61034-2 (L.T. > 60%).

Oil resistant                       : ICEA S-82-552.

Sunlight resistance             : UL 1581 section 1200.
 
RE-m2X(St)HSWAH-CI PIMF FE 180   90° C
 - CU/mc/XLPE/ISCR/OSCR/LSZH/SWA/LSZH - XLPE  insulated, collective screened, armoured, HFFR sheathed cable 500 V
 
Applications
 
These cables are used for transmission of analogue and digital signals in instrumentation and control systems at chemistry and  petrochemistry industry plants, power plants, natural gas and petroleum plants, etc...
These cables fields of use are fire proof and can continue with the supply of a power for a period of 180 minutes under the existing fire conditions.
These cables are used in environments which must have no corrosive gases emitted in the event of fire.
In case of fire, these cables inhibit the propagation of the flames and the development of smoke is extremely low.
Instrumentation cables are not allowed for direct connection to a low impedance source, e.g. public mains electricity supply.
With blue sheath, it is suitable for intrinsically safe systems.
The armour above the inner sheath protects the cable from mechanical shocks.
These cables are recommended for direct burial.
They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.