Categories

LI2Y(St)CYÖ-uv-fl PIMF  *EMC
 - PE insulated, screened, data cable (300/500 V) Maximize

LI2Y(St)CYÖ-uv-fl PIMF *EMC
 - PE insulated, screened, data cable (300/500 V)

LI2Y(St)CYÖ-uv-fl PIMF *EMC
   PE insulated, screened, data cable (300/500 V) - Construction
 

Conductor            : tinned copper wires (7x0,30 mm SnCu).
Insulation             : PE compound, 2Y1.
PIMF construction  : polyester tape above the pair, AL-PES tape
                            over the drain wire (7 wires) 24 AWG stranded (7x32).
Lay-up                 : PIMF laid up in layers of optimum pitch.
Separator             : polyester tape.
Screen                 : with drain wire (7 wires) 24 AWG stranded
                            (7x32) under the AL-PES tape.
Screen                 : braid of tinned CU wires, 90% coverage.
Outer sheath         : PVC compound, UV and oil resistant.
Sheath colour       : RAL 7001, Grey.
*Electromagnetic compatibility

More details

LI2Y(St)CYÖ-uv-fl PIMF *EMC
   PE insulated, screened, data cable (300/500 V) - Technical data and tests
 
Rated voltage           :    0,22 mm² : 350 V;
                                ≥ 0,25 mm²: 500 V;
                               Uo/U  ≥  0,50 mm²: 300/500 V.
Test voltage            :     0,22 mm² : 1200 V;
                              ≥ 0,25 mm² : 1500 V;
                              ≥ 0,50 mm² : 2000 V.

Temperature range   : fixed    : - 30° C ~ + 70° C;
                              mobile :   - 5° C ~ + 70° C.
Min. bending radius : fixed    :   6 x D;
                              mobile : 15 x D.

Insulation resistance : min. 5000 MΩ/km.
Mutual capacitance  : d/d    0,22 mm²: max. 120 pF/m;
  d/d    0,25 mm²: max. 140 pF/m;
Inductance             : ~ 0,4 Mh/km;
Impedance : ~ 85 Ω.
 
LI2Y(St)CYÖ-uv-fl PIMF *EMC
   PE insulated, screened, data cable (300/500 V) - Standards


Cable                  : VDE 0812 & VDE 0814 & VDE 0245.

Conductor           : IEC 60228 Class 2; 

                           DIN EN 60228 Class 2.

Insulation            : VDE 0207-2  (2,20 mm).

Flame  test           : IEC 60332-1 & DIN EN 60332-1.

                            IEC 60332-3 & DIN EN 50266-2-4.
Sunlight resistance : UL 1581 section 1200.

Oil resistance         : ICEA S-82-552.
 
 
LI2Y(St)CYÖ-uv-fl PIMF *EMC
   PE insulated, screened, data cable (300/500 V) - Applications
 

These screened flexible data cable is used in instrumentation and control engineering; in industrial electronics, computers, security systems, information and transmission systems, office machines and for voice frequency transmission.
The screen provides protection against external pulses. These cables are not intended for outdoor or underground installation.

All Rights Reserved Halley Cables © 2006 - 2024