YSLCY - PVC insulated, screened, flexible control cable (300/500 V) Maximize

YSLCY - PVC insulated, screened, flexible control cable (300/500 V)

YSLCY control cable 300/500 V - Construction


Conductor            : flexible copper wires, plain; IEC 60228 Class 5
                             DIN EN 60228 Class 5
Insulation             : PVC compound , TI2
Core identification : according to DIN EN 50334 black cores with
                             white numerals with green/yellow from 3 cores
  
Lay-up                 : cores laid up in layers of optimum pitch
Separator             : polyester tape
Screen                 : braid of tinned copper wires, 85% coverage
Outer sheath        : PVC compound, TM2
Sheath colour       : RAL 7001, Grey
                            (to be agreed upon the shade of grey)

More details

YSLCY control cable 300/500 V - Technical data and tests
Standard                  : HD 21.13 S1, DIN VDE 0281-13; VDE 0245-102.
Insulation resistance  : min. 20 MΩ/km.
Rated voltage Uo/U   : 300 / 500 V.
Test voltage (50 Hz)  : 2000 V.
Temperature range    : fixed    : - 40° C ~ + 70° C; 
  
                                  mobile :   - 5° C ~ + 70° C.
Min. bending radius    : fixed    :   4 x D; 
  
                                  mobile : 10 x D.
 

* Upon request this cable can be produced having a rated voltage of 0.6/1 kV.

* Upon request this cable can be made with 65% braid of tinned copper wires.

* Core identification for coloured cores is according to HD 308 S2.

YSLCY control cable 300/500 V - Applications

These screened flexible and reduced diameter cables are used in mechanical engineering for instrumentation and control equipment, for tooling machinery, production lines, and flexible applications for free movement without tensile load.
The screen protects against external pulses and ensures an interference-free transmission.
These cables should not be used for outdoor or underground installation.

All Rights Reserved Halley Cables © 2006 - 2024