Categories

FG7M1 / FG7OM1
 - Low voltage power cable insulated, halogen free, low emission of smoke, toxic and corrosive gases Maximize

FG7M1 / FG7OM1
 - Low voltage power cable insulated, halogen free, low emission of smoke, toxic and corrosive gases

FG7M1 / FG7OM1
 - Construction

Conductor : flexible copper, class 5.

Insulation  : HEPR, G7 quality.
Filler         : not fibrous and not hygroscopic.

Sheath     : thermoplastic, M1 quality*. 

FG7M1      -  for one core cables.
  
FG7OM1    -  for multiple cores cables. 


* M1 - Suitable for insulation and sheath of cables and wires. This compound is fire retardant, oil and hydrocarbon resistant. It gives cables self – extinguished properties, without halogenidric acids issuing. Furthermore, emissions of toxic, corrosive gases and smoke, during possible fires, are particularly reduced. This compound is suitable also for  flame – retardant cables according to IEC 60331 law.

More details

FG7M1 / FG7OM1 - Technical data and tests

Standards                                       : according to BT 2006/95/EC- RoHS: 2002/95/EC; CEI 20-13 CEI 20-38; 
                                                      CEI UNEL 35382  - 35384; CEI EN 60332-3-24 (CEI 20-22 III);
                                                      CEI EN 60332-1-2; CEI EN 50267-2-1; CEI EN 61034-2; CEI 20-37/4-0.

Nominal voltage U0/U                       : 0,6/1 kV.
Test voltage                                   : 4 kV.
Maximum voltage Um                        : 1,2 kV.
Maximum operating temperature        : 90° C.
Maximum short circuit temperature 
  
for sections up to 240 mm²              : +250° C.
Maximum short circuit temperature 

for sections over 240 mm²               : +220° C.
Min. operating temperature 
  
(without mechanical shocks)            : -15° C.
Minimum installation and use temp.    : 0° C.

Minimum bending radius
per 
D cable diameter (in mm)           : Power flexible cables, class 5  : 4 x D.
 
                                                     Control flexible cables, class 5 : 6 x D.

Max. pulling stress during installation  : 50 N/mm².
Static stress : 15 N/mm².
Packing                                         : drums to agree.
Core colours                                  : Single core   : black.
                                              
       Two cores   : blue-brown.
                                                     Three cores : brown-black-gray (or blue-brown-Y/G).

                                                     Four cores   : blue-brown-black-gray (or Y/G instead blue).
                                                     Five cores    : Y/G-blue-brown-black-gray (or black instead Y/G).
      
                                                     Multicores    : black with numbers.
Sheath colour                                : green.


FG7M1 / FG7OM1 - Applications
This power and control cable can be used for outdoor and indoor applications, even wet. Suitable for fixed installations in open air, in tube or canals, masonry, metal structures, overhead wire and for direct or indirect underground wiring.
The most important property of this kind of cable is its protection against smoke, toxic and corrosive gases in case of fire.

All Rights Reserved Halley Cables © 2006 - 2024