Categories

SIMH-CTRL
 - Silicone sheathed, flexible cable for installations Maximize

SIMH-CTRL
 - Silicone sheathed, flexible cable for installations

SIMH-CTRL silicone sheathed installations cable - Construction

Conductor     : electrolytic twisted copper.

Insulation      : silicone.

Stranding      : twisted at regular intervals
.
Outer sheath : silicone.

More details

SIMH-CTRL silicone sheathed installations cable - Technical data and tests

Operating voltage      : 300/500 V.

Temperature range    : -60° C ~ +180° C.

Min bending radius    : fixed   :   6 x D.

                                 mobile: 10 x D.

Insulation resistance  : > 20 MΩ/km.

Conductor resistance : 0.74 mm² =    26 Ω/km.
      
                                     1 mm² = 19.5 Ω/km.
    
                                  1.5 mm² = 13.3 Ω/km.
  
                                  2.5 mm² = 7.98 Ω/km.

                                     4 mm² =  4.95 Ω/km.

                                     6 mm² =    3.3 Ω/km.
 
SIMH-CTRL silicone sheathed installations cable - Standards
Conductor                  : IEC 60228 class 5, DIN EN 60228 class 5.

Insulation                   : HD 22.1S4 E12 VDE 0282-1.

Insulation color coding : VDE 0293, HD 308 S2.

Outer sheath              : HD 22.1S4 EM9 VDE 0282-1.

Min. bending radius     : IEC 60331-21.

Flame test                  : IEC 60332-1-2, VDE 0482-265-2-1, EN 50265-2-1.

Smoke density            : IEC 61034-2 & DIN EN 50268-2.

Corrosive gas test       : IEC 60754-1-2 & DIN EN 50267-2-3.

Halogen test              : IEC 60754-1, VDE 0482-267-2-1, EN 50267.
 
SIMH-CTRL silicone sheathed installations cable - Applications
This cable is used for command and power feed in environments where the ambient temperature is high and in facilities and machines which operate in dry, moist or wet conditions.
Due to their low mechanical durability, they are not recommended for mobile use.

All Rights Reserved Halley Cables © 2006 - 2024