Categories

H05SSQS-K…(SIMH-S)
 - High temperature operating, silicone inner sheath and armoured cable Maximize

H05SSQS-K…(SIMH-S)
 - High temperature operating, silicone inner sheath and armoured cable

H05SSQS-K…(SIMH-S) high temperature operating cable - Construction


Conductor     : flexible copper wires, plain.
Lay-up          : cores laid up in layers of optimum pitch.
Inner sheath  : silicone rubber compound, EM9.
Armour          : braid of galvanised steel wires, approx. 85 % coverage.
Outer sheath  : silicone rubber compound, EM9.
Sheath colour : oxbrown-red.

More details

H05SSQS-K…(SIMH-S) high temperature operating cable - Technical data and tests

Rated voltage Uo/U          : 300 / 500 V. 

Test voltage (AC 50 Hz)    : 2000 V.

Insulation resistance         : min. 20 MΩ/km.

Temperature at conductor : + 180° C. 

Short circuit temperature   : + 200° C. 

Temperature range           : fixed   : - 60° C ~ + 180° C;

                                        mobile : - 25° C ~ + 180° C. 

Min. bending radius          : fixed    :    4 x D;

                                        mobile : 7,5 x D.
 
H05SSQS-K…(SIMH-S) high temperature operating cable - Standards
Cable                          : VDE 0250, DIN VDE 0282-15 and HD 22.15 S1 (designed according to). 

Conductor construction : IEC 60228 class 5, DIN EN 60228 class 5.

Core identification        : HD 308 S2 & VDE 0293-308.
                                    DIN EN 50334 black cores with white numerals with green/yellow after 5 cores.

Flame retardance test   : IEC 60332-1 & EN 50265-2-1;
  IEC 60332-3 & EN 50266-2-4.

Insulation integrity       : IEC 60331, VDE 0472-814. 
 
H05SSQS-K…(SIMH-S) high temperature operating cable - Applications

These silicone insulated, with inner sheath and steel wire braided armoured cables are used as mobile connection cables for equipment where high temperatures can arise as well as for ambient air temperatures between -60° C and +180° C.
Furthermore, these cables are used in all areas where installation conditions are very difficult and have high mechanical loads e.g in ship building, power plants, cooking plants, glass and ceramic works, foundries, for high power lighting fixtures etc.
The armour above the inner sheath acts as a bedding and protects the cores from any damage from the steel wires.
The steel wire braid serves as protection against mechanical transverse loads and act as a magnetic screen against interference.
The galvanised steel wires are free of corrosion and oxidation.

All Rights Reserved Halley Cables © 2006 - 2024