SILHALL 13.8 kV -60° to +180° C -  Silicone and Heat Resistant Cables (13.8 kV)
 Maximize

SILHALL 13.8 kV -60° to +180° C - Silicone and Heat Resistant Cables (13.8 kV)


SILHALL 13.8 kV -60° to +180° C  Silicone and Heat Resistant Cable (13.8 kV) - 
Construction
 

Conductor     : tinned copper, stranded, class 5.

Separator      : semi-conducting tape.

Insulation     : silicone rubber.

Outer sheath : coated synthetic reinforcing braid.

More details

SILHALL 13.8 kV -60° to +180° C  Silicone and Heat Resistant Cable (13.8 kV) - Technical data and tests
 

Working voltage                : 15 kV.

Test voltage                      : 30 kV.

Max. operating temp., fixed : -60° C ~ +180° C, peaks at +230° C.

Min. bending radius, fixed   : ~5 x D.
 
SILHALL 13.8 kV -60° to +180° C  Silicone and Heat Resistant Cable (13.8 kV) - Options
 

UL/CSA approval, 15 kV            : style 3664.

Other working voltages              : 1.1 kV, 3.7 kV, 6.6 kV.

Version without reinforcing braid : consult us.

Other cross-sections                  : consult us.
 
SILHALL 13.8 kV -60° to +180° C  Silicone and Heat Resistant Cable (13.8 kV) - Standards & Approvals
Fi rated as per NF F 16-101.

Type approval certificates for use in ship building
 industry, IEC 60092-350 standards.

Lloyd’s Register of Shipping and Bureau Veritas.

Fire behaviour : meets requirements of IEC 60331-21,
 IEC 60332-1 and IEC 60332-3-22.
 
SILHALL 13.8 kV -60° to +180° C  Silicone and Heat Resistant Cable (13.8 kV) - Additional information


Good resistance to thermal shock and UV.

Excellent ageing resistance.

Good resistance to ozone and the corona effect.

Excellent mechanical strength.

Compatible with most impregnation varnishes.

Max. permissible current: consult our technical
departments.

Packaging can be in rolls, spools or drums.
 
SILHALL 13.8 kV -60° to +180° C  Silicone and Heat Resistant Cable (13.8 kV) - Applications


Flexible connecting cable for increased ambient temperatures, for example transformers, generators and motors.
For installation indoors and in cable ducts for power stations, industry and distribution networks etc.
The halogen-free sheath/protection is resistant against transformer oil and fuel oil.
The cable is also suited for wiring of rotating machines: motors, alternators, generators, wiring of static motors: transformers, inductors, inverters, choppers for shipbuilding and railway construction, power supply.